Amp Chart
Amp Chart
Lead Wire Current Carrying Capacity (Ampacity)
AWG SIZE | Insulated Conductor Temperature Rating | AWG SIZE | |||||
at 80°C | at 90°C | at 105°C | at 125°C | at 150°C | at 200°C | ||
40 | 0.33 | 0.49 | 0.55 | 0.60 | 0.71 | 0.78 | 40 |
38 | 0.47 | 0.68 | 0.77 | 0.84 | 0.98 | 1.1 | 38 |
36 | 0.63 | 0.91 | 1.0 | 1.1 | 1.3 | 1.5 | 36 |
34 | 0.87 | 1.2 | 1.4 | 1.5 | 1.8 | 2.0 | 34 |
32 | 1.2 | 1.7 | 1.9 | 2.1 | 2.4 | 2.7 | 32 |
30 | 2.0 | 2.2 | 2.5 | 2.8 | 3.2 | 3.6 | 30 |
28 | 3.0 | 3.0 | 3.4 | 3.7 | 4.3 | 4.8 | 28 |
26 | 4.0 | 4.0 | 4.6 | 5.0 | 5.7 | 6.4 | 26 |
24 | 5.0 | 5.5 | 6.2 | 6.7 | 7.7 | 8.7 | 24 |
22 | 8 | 10 | 11 | 12 | 14 | 16 | 22 |
20 | 10 | 13 | 14 | 15 | 18 | 21 | 20 |
18 | 15 | 18 | 20 | 22 | 24 | 28 | 18 |
16 | 19 | 24 | 26 | 28 | 31 | 35 | 16 |
14 | 27 | 35 | 39 | 42 | 46 | 54 | 14 |
12 | 36 | 40 | 51 | 55 | 60 | 68 | 12 |
10 | 47 | 55 | 67 | 72 | 80 | 90 | 10 |
8 | 65 | 80 | 90 | 97 | 106 | 124 | 8 |
6 | 95 | 105 | 121 | 131 | 155 | 165 | 6 |
4 | 125 | 140 | 160 | 172 | 190 | 220 | 4 |
3 | 145 | 165 | 180 | 194 | 214 | 252 | 3 |
2 | 170 | 190 | 215 | 232 | 255 | 293 | 2 |
1 | 200 | 220 | 247 | 266 | 293 | 344 | 1 |
1/0 | 230 | 260 | 286 | 309 | 339 | 399 | 1/0 |
2/0 | 270 | 300 | 329 | 355 | 390 | 467 | 2/0 |
3/0 | 315 | 350 | 380 | 410 | 451 | 546 | 3/0 |
4/0 | 370 | 405 | 446 | 481 | 529 | 629 | 4/0 |
Multiply the ampacity rating from above by the correction factor listed below to determine the ampacity rating of a conductor in a multi-conductor cable.
Multiple Conductor Correction Factors | ||
Number of Conductors | Multiply ampacity by factor | |
4-6 | 0.80 | |
7-9 | 0.70 | |
10-20 | 0.50 | |
21-30 | 0.45 | |
31-40 | 0.40 | |
41+ | 0.35 |